Santa Clara Data Center 04

  • Santa Clara Colocation Facility 04 Santa Clara Colocation Facility 04

Quick Overview

Our Santa Clara Facility 04 is just over 67,000 square feet. Power is provided from multiple Silicon Valley substations. It is a carrier neutral facility. Key card access is required at every building entrance. On-site guards patrol both the inside and outside of the facility.

Santa Clara Data Center 04 Details

Square Footage: 67,179 square foot facility. 60,000+ square feet of raised floors (across 2 levels). 36,742 square feet 1st floor; 30,437 square feet 2nd floor.
Power Specs: Multiple, Silicon Valley Power, substations feed dual feed power to the facility at our primary switchgear (PSG); Power delivered to the four transformers, stepped down from 12kV to 480V, and sent to the ATS’s; Load is distributed through our four main switchboards, MSB1, MSB2, MSB3 and MSB4. The facility is supported by seven emergency generators: 2-1250kw units for the first floor and 4-1000kw units for the second floor. The ATS’s offer protection from power failure; The MSB’s can be tied together to provide power in case of an ATS failure; UPS units redundant at the static switch level; Dual cord equipment offers protection from PDU failure. Seven Liebert 750kVA UPS provide conditioned power for the first and second floors data center. Fuel– 10,200 gallons capacity of diesel fuel on site with refueling contracts. All power cabling below floors is waterproof conduit encased, with waterproof connectors to all equipment.
Carrier Specs:
Carrier-neutral facility providing access to multiple providers for local, fiber and Internet connectivity. From low speed 56kbps to Optical carrier level services are available. Internal cabling: Copper or fiber access to carrier bandwidth using cable management trays throughout building. External Cabling: Multiple secure entrances into building including multiple CO redundancy and fiber access to primary carriers.
Security: All building entrances require card key access; Data center floor and secured areas require card key and biometric authentication. Guards on site 24/7/365; Active patrols both inside and outside the facility. Over 54 cameras cover inside and exterior of building, all entrances, alternate workspace, and data center floor. Cooling – four state of the art chillers provide cooling to the data center floor and non-critical office space. N+1 Chiller plant. Smoke detection sensors above and below raised floor. The IDC and associated support areas are equipped with a both dual action dry sprinkler systems and Fenwal FM-200 fire detection and suppression system; Detectors (photo and ion) are located under the raised floor, at ceiling level, and above the ceiling (on the second floor pan); System equipped with FM-200 release nozzles under floor and at the ceiling; The activation of two detectors will start a 30 second time delay; Following the delay, the pre-action pipes fill with water, the FM-200 agent is released, and an the facility is protected by EPO.

Additional Information

City Santa Clara
State California
Country United States
Colocation 0
Cloud Computing 0
Disaster Avoidance No
Managed Services 0
Special Services No
Base Rack Price 0
Carrier Neutral Call
Max Power/Cabinet Call
Minimum Contract Time 1 Year
Minimum Space Lease 0
Multiple Power Feeds 0
SSAE16 Certified 0
Space Available Yes
Tier Call
Total Facility Square Footage 0
Total Power Call
N1/N2 Architecture 0